OperatingVoltageRange | DC24V |
Alarm Current | Maximum 70 mA @ 24 VDC |
Alarm Sound Intensity | Minimum 95dB |
Operating Humidity Range | 10% to 93% Relative Humidity, Non-condensing |
Operating Temperature Range | -10°Cto50°C(14°Fto122°F) |
Input terminal Wire Gauge | 12 to 18 AWG |
Dimensions | Diameter150mm, Height45mm |
OperatingVoltageRange:DC24V
Alarm Current:Maximum 70 mA @ 24 VDC
Alarm Sound Intensity:Minimum 95dB
OperatingHumidityRange:10% to 93% Relative Humidity, Non-condensing
OperatingTemperatureRange:-10°Cto50°C(14°Fto122°F)
Input terminal to 18 AWG
Dimensions:Diameter150mm, Height45mm
Weight:Net Weight670g, Gross Weight720g
The AS-BELL Electric bell of notification appliances offers a wide range of Sound, for wall and ceiling applications, indoors and outdoors. They are designed to be used in 24 volt DC systems.
The system designer must make sure that the total current drawn by the devices on the loop does not exceed the current capability of the panel supply, and that the last device on the circuit is operated within its rated voltage.
When calculating the voltage available to the last device, it is necessary to consider the voltage drop due to the resistance of the ker the ler the voltage drops. e tables can be obtained from electrical handbooks.