Quick Details
- AC Voltage Output:57.7V, 100V, 220V, 380V or 69.3V, 120V, 240V, 480V( optional)
- AC Current Output:200mA, 1A, 5A, 20A, 100A
- Frequency Output:45Hz-65Hz
- Harmonic:2-51times
- Dimensions (W*D*H) (mm):500*600*175
- Weight:27kg
- Processing Time:7 days
- Port:Tianjin
- Supply Ability: 5000 Sets Per Week
- Brand Name:GFUVE
GFUVE Kwh Meter Calibration Test Bench
GF302D Portable Three Phase Energy Meter Calibrtaion
Able to test basic error, shunt running, start, standard error automatically and manually in single-step of single/three phase, according to relative regulation of kWh meter.
Able to do change test caused by voltage influence, frequency influence and harmonic influence.
Output of power source is speedy and stable, AC maximum output of each phase can reach 120A in maximum.
Voltage, current and phase position of each phase can be adjusted in split-phase, improving the flexibility of power source.
Frequency of each impulse input port can reach 40Hz.
7-inch TFT color display touch screen, English menu, simple and convenient operation, commonly used functions and current basic load point can be controlled in one button.
Each meter position can provide one standard, dependent RS485 port, and able to perform multi-function test, such as communication test.
Impulse port of each meter position, external polarity can be set randomly, able to adapt kWh meter of impulse cascade and common-anode.
PARAMETERS
Electrical parameters
Accuracy
0.05%, 0.1%
Power Supply
One Phase AC 180-265V, frequency 50/60Hz.
AC Voltage Output
Range(U1,U2,U3)
57.7V, 100V, 220V, 380V
or 69.3V, 120V, 240V, 480V( optional)
Adjustment range
(0-120)%RG(1)
Adjustment fineness
0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability
0.01%/120s
Distortion
0.3% (Non-capacitive load)
Output load
each phase 25VA
Measuring accuracy
0.05%RG
AC Current Output
Range(I1,I2,I3)
200mA, 1A, 5A, 20A, 100A
Adjustment range
(0-120)%RG
Adjustment fineness
0.01%RG, 0.1%RG, 1%RG, 10%RG as optional.
Stability
<0.01%/120s
Distortion
≤0.3% (Non-capacitive load)
Output load
45VA
Accuracy
0.05%RG
Power Output
Active power output stability
<0.01%RG/120s
Reactive power output stability
<0.02%RG/120s
Active power measuring accuracy
0.05%RG
Reactive power measuring accuracy
0.1%RG
Phase Output
Output adjustment range
0°-359.999°
Output adjustment fineness
10, 1, 0.1, 0.01 as optional.
Resolution
0.01°
Accuracy
0.05°
Power Factor
Adjustment range
-1 ~ 0 ~ 1
Resolution
0.0001
Measurement accuracy
0. 0005
Frequency Output
Adjustment range
45Hz-65Hz
Output adjustment fineness
5Hz, 1Hz, 0.1Hz, 0.01Hz as optional.
Resolution
0.001Hz
Accuracy
0.005Hz
Voltage /Current/Harmonic Setting
Harmonic number
2-51times
Harmonic content
0-40%
Harmonic phase
0-359.99
Harmonic setting accuracy
(10%±0.1%)RD(2)
Power Energy Measurement Error
Active power energy
0.05%RG
Reactive power energy
0.1%RG
Power Pulse Output
Power pulse type
active pulse, reactive pulse
Active power pulse output
5V, 10mA
Power Pulse Input
Energy pulse type
support active and reactive pulse, the highest frequency power pulse input is 180K.
Mechanical parameters
Dimensions (W×D×H) (mm)
500x600x175
Weight (kg)
About 27
(1) RG means range, the same as below;
(2) RD means the setted harmonic content, harmonic can be a single output, also multiple output.