The new generation of intelligence has the functions of electricity calculation,accident analysis , motor error reporting and so on in addtion to conventional low-voltage motor protection, monitoring, control functions. Using the motor protect and control system to improve company's reliability and safety will improve the company's automatic management level for the functioning motors. GY806 motor control protector uses the LCD screen to display all the functioning motor's datas like three-se voltage,three-se current,power factor,each time/total electricity,rate,power,error message,alarming value,total operating time and so on to complete the remote automatic control,direct control ,terminal control,forward and reverse stratup control,star triangle startup control,auto step-down control,direct bypass control to the motor.Its fieldbus RS5485 interfaces support various protocols which can be used in many microcomputer industrial control configuration software to complete the network communication management,on the other hand, it can also connect with the DCS system by the way of 4-20 Ma variable hen transmit and output the operating parameters of the motor to form a distributed integrated electric power monitoring system to carry out a variety of control such as remote measurement&control, remote communication,remote control, protection, setting. GY806 motor control protector is designed with software,hardware and EMC self-calibration function, and has super anti-interference ability and the reliability of accurate and sensitive action.Its size is small and its structure is compact,so it can be straightly installed in Low voltage control terminal cabinet and each kind of 1/4 and above drawers by screw or lead rail,it is especially fit for scientific and effective industrial level protection and measure&protect module .
Function Summary
ProtectFunction | Basic Functions | Standard | Match | Remark |
overvoltage protection | â | function after alarmed 3 seconds | ||
undervoltage protection | â | function after alarmed 3 seconds("0"stop fuction) | ||
overload protection | â | current value,function time settable | ||
underload protection | â | |||
locked-rotor protection | â | multiples of locked-rotor settable | ||
open-se protection | â | function after alarmed 3 seconds | ||
leakage protection | â | set the value of the leakage current | ||
timeout protection | â | start time delay setting according to the equipment need | ||
reversal protection | â | function by automatic judgement | ||
feeder protection | â | |||
electric shock protection | â | Automatic recovery within three seconds | ||
external fault protection | â | function by automatic judgement | ||
electric delay protection | â | delay time settable | ||
ControlFuction | directly start-up | â | select wiring according to the start-up modeset the change-over time and start-up mode | |
star triangulation start | â | |||
direct bypass start | â | |||
forward and reverse stratup | â | |||
step-down start | â | |||
Fault Reset | manual reset | â | time automatic reset or "0" shutoff to manual reset are selectable | |
automatic reset | â | |||
Control Authority | front-panel control | â | set the control and protection rights | |
remote terminal control | â | |||
fieldbus control | â | |||
Measure Function | three-se current | â | monitor module | |
age | â | |||
three-se voltage | â | |||
leakage current | â | |||
rate power | â | |||
power factor apparent power | â | |||
elctricity | â | |||
Communication Function | RS485interfaces/ Mdobus-RTU | â | protocol | |
Analog Output | One channel DC4-20mA | â | internal DC24V power supply | |
Switch Output | 6-channel optoelectronicbarrier input,function editable | â | ||
Control Output | 6-channel relay output,function editable | â | rivet capacity 5A | |
Set Reminding | full screen chinese | â | LCD display | |
Fault Query | last ten fault query | â | ||
Time Query | accumulated or current time function time query | â | ||
Parameter Query | function,set-up,fault message,electric power,rate,apparent power | â |
Technical Parameter
Work power | AC/DC 85~265V 50Hz | |||||
Power supply circuit voltage | â¤AC1160 | |||||
Control the relay output | passive 5A | |||||
Install mode | standard 35mm lead rail installation or screw fix. | |||||
Field of application | three-se power supply equipment | |||||
Overvoltage protection | set the voltage value | 110~465 V settable | ||||
Undervoltage protection | set the voltage value | 0~380V settable | ||||
Overload protection | current setting | A settable within standard current | ||||
function time | 1~255S settable | |||||
Underload protection | current setting | A settable within standard current | ||||
function time | 0~255S settable | |||||
Open-se protection | percentage setting | 1~100% settable | ||||
Leakage protection | leakage current value setting | 50~5000mA settable | ||||
function controlled through programming | ||||||
Locked-rotor protection | multiples setting | 1~9 multiples settable | ||||
Timeout protection | start-up delay time setting | 1~255S settable | ||||
Fault reset | manual reset | be"0" | ||||
automatic reset | 0~255S settable | |||||
20mA corresponding current | set 20mA corresponding current value output | |||||
Communication address | the device communication address | 1~255 machine settable | ||||
Startup type | select startup type | direct startup, star triangle startup ,forward and reverse startup, direct bypass , forward and reverse bypass startup,step-down startup settable | ||||
Relay transfer time | transfer time | 1~250S settable | ||||
Programmable relay style | startup delay close,leakage delay close,fault shutdown close,power on delay close,alarming delay close setable,low power factor alarming closed | |||||
Programmable relay output time | output delay time | 1~250S settable |
Programmable relay style | startup delay close,leakage delay close,fault shutdown close,power on delay close,alarming delay close setable,low power factor alarming closed | |
Programmable relay output time | output delay time | 1~250S settable |
Overload control protection | when the motor is overload,the over current will be calculated according to the motor heat capacity tracking.Fully considered the motor rotor and stator's temperature rise and the influence to the motor heating because of the three-se unbalance.When the current reached the control protection value,the device will do the alarming and notice the shutdown delay time. | |
Underload protection | when any one of the three-se current is lower than the set underload value,the device will do the alarming and notice the shutdown delay time. | |
Locked-rotor protection | when the current value reached the set current multiples,the protection device will do the alarming and notice the shutdown delay time. | |
Three-se current unbalance protection | when the ratio of the minimum se or the maximum ent reaches or exceeds the set value, the protection device will do the alarming and notice the shutdown delay time. | |
Open-se protection | It will be judged as open-se fault if any one of the three-se current's ratio is not bigger than the unbalanced angle value, the device will do the alarming and notice the shutdown delay time. | |
Overvoltage protection | The protection device and the measure device monitor the three-se voltage value, the device will do the alarming and notice the shutdown delay time if the equipment's largest voltage is higher than the set value. | |
Undervoltage protection | The protection device and the measure device monitor the three-se voltage value, the device will do the alarming and notice the shutdown delay time if the equipment's smallest voltage is lower than the set value. | |
Leakage (earth)protection | Judge the leakage fault by using the zero sequence current transformer to measure the protective conductor(PE)or (PEN)'s short-circuit leakage current value.When the short-circuit leakage current value is bigger than the set leakage value, the device will do the alarming and notice the shutdown delay time. | |
Electric shock protection | The protection device monitors the equipment's voltage continuously,when the system voltage recovered after the moment dropped,the motor can start again. | |
Timeout protection | The protection device inspects the start-up current delay time,when the equipment can bot be started up within the start-up delay time,and the three -se current is 1.2 time bigger than set current,the timeout protection will function and the power will turn off. | |
Reversal protection | When the protection device monitored the three-se voltage sequence is not correct,the equipment can not start-up. | |
External fault protection | When the device monitored the external switching value input ent from the device's set switching value input e can not be started up. |
Current specification
Model | Power range | Current range | remark |
30/5A | 0.55Kw-3.7Kw | 0.6A-30A | Provide 3 pieces of turns ratio BH0.66 current tranformers,The ratio can set freely |
50/5A | 3 Kw-12 Kw | 1A-50A | |
100/5A | 10 Kw-30 Kw | 10A-100A | |
150/5A | 20 Kw-50 Kw | 15A-150A | |
200/5A | 37 Kw-90 Kw | 20A-200A | |
300/5A | 75 Kw-132 Kw | 30A-300A | |
400/5A | 90 Kw-200 Kw | 40A-400A | |
600/5A | 110 Kw-300 Kw | 60A-600A | |
800/5A | 155 Kw-400 Kw | 80A-800A | |
1000/5A | 220 Kw-450 Kw | 100A-1000A | |
1500/5A | 450 Kw-750 Kw | 150A-1500A |