1.GeneralHVD32 12KV This vacuum circuit breaker VCB is three-se AC 50Hz, rated voltage 12 kV outdoor high voltage switch equipment. It is mainly used to opening(closing) load current, overload current and short-circuit current. It is suitable to protect or control the city or village electrical power distribution system.
No. | item | unit | Parameter | ||
1 | Rated voltage | KV | 12 | ||
2 | Rated frequency | Hz | 50 | ||
3 | The 1min rated power frequency withstand voltage | KV | se to se, to Ground42 / Fracture 48 | ||
4 | Rated lightning impulse withstand voltage(peak) | KV | se to se, to Ground42 / Fracture 48 | ||
5 | Rated short-circuit breaking current | KA | 12.5 | 16 | 20 |
6 | Rated current | A | 630 | ||
7 | Rated peak withstand current | KA | 31.5 | 40 | 50 |
8 | 4s rated short time withstand current | KA | 12.5 | 16 | 20 |
9 | Rated operating sequence | O-0.3s-CO-180s-CO(Electric operation) | |||
10 | Rated short circuit breaking current breaking times | times | 30 | ||
11 | Mechanical life | times | 10000 | ||
12 | Secondary circuit 1min power frequency withstand voltage | V | 2000 | ||
13 | Opening time(rated voltage) | ms | 30-60 | ||
14 | Closing time(rated voltage) | ms | 20-40 | ||
15 | Energy storage motor rated power | W | 40 | ||
16 | Energy storage motor rated voltage | V | DC220/110 | ||
17 | Rated closing operation voltage | V | DC220/110, AC220/110 | ||
18 | Rated switching operation voltage | V | DC220/110, AC220/110 | ||
19 | Electric energy storage time | â¤8 |