Portable CT Analyzer

Model: CTP-200P

Portable CT Analyzer CTP-200P is capable of testing Protection CTs, Measuring CTs, TP class CTs and inductive PTs according to IEC61869-2(IEC60044-1,60044-6), IEC61869-3(IEC60044-2), IEEE/ANSI C57.13 etc. test standards. It allows to test the knee-point voltage up to 40kV CTs and PTs on-site in power grids or in manufacturers' production facilities or test labs.

Portable CT Analyzer CTP-200P is an all-in-one solution for measuring all parameters without the need for any further equipment(such as a burden box).

The weight of Portable CT Analyzer CTP-200P is only 9kg(19.84 lbs), which is easy to be carried by testing engineers.

Main Features

●Able to test Protection CTs, Measuring CTs, TP class CTs and inductive PTs

●Test excitation characteristic and error curve based on low-frequency measurement principle

●Measure ratio, polarity, ratio error and se displacement error based on voltage method

●Adopt patented multifunctional rotary mouse to replace the keypad

●Adopt 5.7 inches LCD screen for display

●Adopt DSP, ARM and embedded LINUX operation system

●Both local test and PC remote test available

●Higher measurement accuracy: 0.05 %

●Print test results directly by built-in thermal printer

●Small and light weight (9kg / 19.84 lbs) for easy transport

Technical Data

●Test Standard: IEC61869-2(IEC60044-1,60044-6), IEC61869-3(IEC60044-2), IEEE/ANSI C57.13

●Maximum Knee Voltage Measurement: 40kV

●Output Range:

voltage: 0~180V(RMS)

current: 0~12A(RMS), 36A(peak value)

●Voltage Measurement Accuracy: ±0.05%

●CT Ratio Measurement:

range:1~30000

accuracy: ±0.05%

●PT Ratio Measurement:

range:1~10000

accuracy: ±0.05%

●se Measurement:

accuracy: ±2min

resolution: 0.01min

●Secondary Winding Resistance Measurement:

range: 0~300Ω

accuracy: 0.1%±1mΩ

●Burden Measurement:

range: 0~300VA

accuracy: 0.1%±0.1VA

●Memory Capacity: >3000 groups test results

●Power Supply

Nominal input voltagecustomized (AC230V/120V±10%, 1-se)
Nominal frequency50/60 Hz
Rated current10A at 230V / 12A at 120V
Connectionstandard AC socket (IEC 60320)

●Environmental Conditions

Operation temperature0 ... +50 °C (+32 ... +122 °F)
Storage temperature-25 ... +70 °C (-13 ... +158 °F)
Humidity rangerelative humidity 5 ... 95 %, non-condensing
VibrationIEC 60068-2-6(20m/s2 at 10 ... 150 Hz)

●Misneous

Weight9kg(19.84 lbs)
Dimensions (W x H x D, without handle)340×300×150mm(13.39x11.81x5.91 in)
Connection port2 USB2.0 ports, 1 communication port

Portable CT Analyzer CTP-200P is the powerful tool for testing Current Transformers and Voltage Transformers.

Premium Services
Get Targeted Quotations
Girl Right
Cross Popup
Arrow 2

I Am :

Signup today to claim your Discount. Get Started before it's too late!

Arrow 1
We use cookies to ensure that we give you the best experience on our website. If you continue to use this site we will assume that you are happy with it. Ok