This isolated barrier is used for intrinsic safety applications. It is a highly configurable timer that accepts a digital nsor/mechanical from a hazardous area and is commonly used in applications requiring on-delay, off-delay, one-shot, or pulse lengthening. The output relay switch duration is easily adjusted, and a pulse divider function allows step-down ratios from 1:1 to 9999:1. A reset can be activated via dry switch and used to terminate a particular time function. The unit is easily programmed by the use of a keypad located on the front of the unit. t detection of the field circuit is indicated by a red LED. For additional information, refer to the manual and .
General specifications
| Digital Input |
Supply
Connection | terminals 23, 24 |
Rated voltage | 115 V AC ± 10 % |
Rated current | 35 mA |
Power consumption | 4 VA |
Input
Connection side | field side |
Connection | Input I: terminals 1+, 3- , input II: terminals 13+, 14- |
Input I | acc. to EN 60947-5-6 (NAMUR), see manual for electrical data |
| Open circuit voltage/short-circuit current | 8.2 V / 10 mA |
| Switching point/switching hysteresis | 1.2 ... 2.1 mA / approx. 0.2 mA |
| Pulse duration | min. 75 µ,s / 1 ms see instruction manuals, the maximum input frequency has to be observed. |
| Input frequency | 0 ... 80 Hz , pulse divider 0 ... 1 kHz |
| t detection | breakage I &le, 0.15 mA, short-circuit I > 6.5 mA |
Input II | reset |
| Active/Passive | I > 3 mA / I < 1.5 mA |
| Open circuit voltage/short-circuit current | 12 V / 3.5 mA |
| Pulse duration | min. 10 ms |
Output
Connection side | control side |
Connection | output I: terminals 10, 11, 12 , output II: terminals 19+, 20- |
Output I | utput |
| loading | 253 V AC/ 2 A / cos &, &ge, 0.7 , 40 V DC/ 2 A |
| Mechanical life | 5 x 107 switching cycles |
| Energized/De-energized delay | approx. 20 ms / approx. 20 ms |
Output II | nic unit, isolated |
| loading | 40 V / 50 mA |
| Energized/De-energized delay | after rising input flank 3 ms , after falling input flank 2 ms |
| > | 1-5 V (50 mA, short-circuit/overload proof) 0-output (off-state current &le, 10 µ,A) |
Transfer characteristics
Input I | |
| Resolution | < 0.1 % of the set value, min. 10 ms |
| Accuracy | 2 ms |
| Influence of ambient temperature | 0.003 %/K (50 ppm) |
Galvanic isolation
Input I/other circuits | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output I/power supply and reset | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output I, II against eachother | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output II/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Output II/reset | basic insulation according to IEC/EN 61010-1, rated insulation voltage 50 Veff |
Reset/power supply | reinforced insulation according to IEC/EN 61010-1, rated insulation voltage 300 Veff |
Indicators/settings
Display LEDs , display |
Control Control panel |
Configuration | via operating buttons |
Labeling | space for labeling at the front |
Directive conformity
Electromagnetic compatibility | |
| Directive 2014/30/EU | EN 61326-1:2013 (industrial locations) |
Low voltage | |
| Directive 2014/35/EU | EN 61010-1:2010 |
Conformity
Electromagnetic compatibility | NE 21:2006 |
Degree of protection | IEC 60529:2001 |
Ambient conditions
Ambient temperature | -20 ... 60 °C (-4 ... 140 °F) |
Mechanical specifications
Degree of protection | IP20 |
Connection | screw terminals |
Mass | approx. 300 g |
Dimensions | 40 x 119 x 115 mm (1.6 x 4.7 x 4.5 inch) , housing type C3 |
Mounting | on 35 mm DIN mounting rail acc. to EN 60715:2001 |
Data for application in connection with hazardous areas
EU-type examination certificate | TÃV 99 ATEX 1408 |
| Marking | II (1)G [Ex ia Ga] IIC II (1)D [Ex ia Da] IIIC I (M1) [Ex ia Ma] I |
Supply | |
| Maximum safe voltage | 253 V AC (Attention! The rated voltage can be lower.) |
Input I | terminals 1+, 3-: Ex ia |
| Voltage Uo | 10.1 V |
| Current Io | 13.5 mA |
| Power Po | 34 mW (aracteristic) |
Input II | terminals 13+, 14- non-intrinsically safe |
| Maximum safe voltage Um | 40 V (Attention! The rated voltage can be lower.) |
Output I | terminals 10, 11, 12 non-intrinsically safe |
| loading | 253 V AC/2 A/cos &, > 0.7, 40 V DC/2 A resistive load (TÃV 99 ATEX 1408) 50 V AC/2 A/cos &, > 0.7, 40 V DC/2 A resistive load (TÃV 02 ATEX 1885 X) |
| Maximum safe voltage | 253 V (Attention! The rated voltage can be lower.) |
Output II | terminals 19+, 20- non-intrinsically safe |
| Maximum safe voltage | 40 V (Attention! The rated voltage can be lower.) |
Certificate | TÃV 02 ATEX 1885 X |
| Marking | II 3G Ex nA nC IIC T4 Gc |
Output I | |
| loading | 50 V AC/2 A/cos &, > 0.7, 40 V DC/1 A resistive load |
Galvanic isolation | |
| Input I/other circuits | safe electrical isolation acc. to IEC/EN 60079-11, voltage peak value 375 V |
Directive conformity | |
| Directive 2014/34/EU | EN 60079-0:2012+A11:2013 , EN 60079-11:2012 , EN 60079-15:2010 |
International approvals
FM approval | |
| Control drawing | 116-0305 |
UL approval | E223772 |
IECEx approval | IECEx TUN 03.0000 |
| Approved for | [Ex ia Ga] IIC, [Ex ia Da] IIIC, [Ex ia Ma] I |
General information
Supplementary information | Observe the certificates, declarations of conformity, instruction manuals, and manuals where applicable. For information see . |