- AS-Interface certificate
- PELV/SELV
- LED operating display
- 8 A output load
- 115 V AC / 230 V AC switchable
- AS-Interface data decoupling
- Overload protection using FUSE mode
The primary pulsed DIN rail power pack is used for special power supply of AS-Interface networks via a two-supplies a fully loaded AS-Interface system with an output current of 8 A. The voltage input range of the device can be selected on the front side. This makes it possible to operate the device on all single-se power supply voltages commonly used worldwide. Certification of the device according to international and various national standards allows for worldwide usage. Safe operation using FUSE mode: To protect against overload and excess temperature, the device has a FUSE mode (electronically simulated fuse), for permanent shutoff of the output in the event of failure. This turns off the device in the event of overload, short circuit or excess temperature, thus protecting the AS-Interface cable and the attached components. A flashing LED indicates that the FUSE mode has been triggered. Turning the device on again requires deliberately pressing a Reset button on the front side of the unit. This prevents unwanted startup from occurring. Operation without the AS-Interface string: This AS-Interface power pack has an inductive output. For operation without the AS-Interface string (for example lab measurements) we recommend connecting a 470 μF/35 V capacitor between AS-Interface + and AS-Interface -. Standard commercial laboratory loads frequently tend to oscillate and together with the data decoupling form a resonance that exceeds the permitted modulation voltage.
Product Description
AS-Interface power supply, data decoupling, 8 A |
General specifications
UL File /td> | E223176 |
MTBF | 100 a |
Indicators/operating means
Reset push-button switch | FUSE mode reset |
Power selection switch | changeover switch for 115 V AC/230 V AC |
LED Overload | red LED, flashes in the FUSE mode |
LED IR on | red LED: ON: Plug-in jumper position 2-3 OFF: Plug-in jumper position 1-2 |
Plug-in jumper | Position 1-2: Communication Mode Position 2-3: IR addressing |
LED AS-i ok | operating display, LED green |
Electrical specifications
Fusing | T8A/250 V AC HBC (not accessible) |
Capacity factor | > 0.5 |
Rated operating voltage | nominal: 100 ... 120 V AC/220 ... 240 V AC (front end selectable) permissible: 85 ... 132 V AC/184 ... 264 V AC/230 ... 375 V DC |
Rated operating current | 6,0 A (Switch position 115 V) 2.8 A (Switch position 230 V) |
Supply frequency | 47 ... 63 Hz or DC |
Efficiency | typ. 92 % (at 230 V AC/8 A) |
Surge protection | limited to max. 55 V |
Output
Short-circuit protection/overload | FUSE Mode (2 ... 5 s current, then trips) |
Current limit | > 8.4 A |
Voltage | 30.55 V DC ± 3 % |
Current | 8 A |
Galvanic isolation | overvoltage category III |
Residual ripple | &le, 50 mVss (500 kHz bandwidth, 50-&Omega,-measurement with ohmic load) |
Short-circuit current | 12 ... 25 A (max. 5 s) |
Standard conformity
Electromagnetic compatibility | emitted interference in accordance with EN 50081-2 class B (EN 55011, EN 55022) noise immunity in accordance with EN 61000-6-2, EN 61000-4-2 to EN 61000-4-6, EN 61000-4-11 |
Ambient conditions
Ambient temperature | -10 ... 70 °C (14 ... 158 °F) (Measured 25 mm below the device) from 60° C 6W/°C power recovery necessary |
Storage temperature | -25 ... 85 °C (-13 ... 185 °F) |
Pollution degree | 2 |
Mechanical specifications
Degree of protection | IP20 according to EN 60529 |
Protection class | 1 (IEC 60536), Protective conductor connection necessary |
Connection | Connection terminals, max. conductor cross-section flexible: 0.5 ... 4 mm2 fixed: 0.5 ... 6 mm2 stripped length 7 mm, connector sleeves are permissible |
Material | |
| Housing | metal |
Mass | approx. 890 g |