AS-Interface power supply VAN-115/230AC-K16

  • Origin: Germany

Supplier Info.

  • Company Name FAMAGA GROUP
  • Membership:Free
  • Business Type: Distributor/Wholesaler
  • Employees Total 11-50
  • Annual Revenue
  • AS-Interface certificate
  • PELV/SELV
  • LED operating display
  • 8 A output load
  • 115 V AC / 230 V AC switchable
  • AS-Interface data decoupling
  • Overload protection using FUSE mode
The primary pulsed DIN rail power pack is used for special power supply of AS-Interface networks via a two-supplies a fully loaded AS-Interface system with an output current of 8 A. The voltage input range of the device can be selected on the front side. This makes it possible to operate the device on all single-se power supply voltages commonly used worldwide. Certification of the device according to international and various national standards allows for worldwide usage. Safe operation using FUSE mode: To protect against overload and excess temperature, the device has a FUSE mode (electronically simulated fuse), for permanent shutoff of the output in the event of failure. This turns off the device in the event of overload, short circuit or excess temperature, thus protecting the AS-Interface cable and the attached components. A flashing LED indicates that the FUSE mode has been triggered. Turning the device on again requires deliberately pressing a Reset button on the front side of the unit. This prevents unwanted startup from occurring. Operation without the AS-Interface string: This AS-Interface power pack has an inductive output. For operation without the AS-Interface string (for example lab measurements) we recommend connecting a 470 μF/35 V capacitor between AS-Interface + and AS-Interface -. Standard commercial laboratory loads frequently tend to oscillate and together with the data decoupling form a resonance that exceeds the permitted modulation voltage. Product Description
AS-Interface power supply, data decoupling, 8 A
General specifications Indicators/operating means Electrical specifications Output Standard conformity Ambient conditions Mechanical specifications
UL File /td>E223176
MTBF100 a
Reset push-button switchFUSE mode reset
Power selection switchchangeover switch for 115 V AC/230 V AC
LED Overloadred LED, flashes in the FUSE mode
LED IR onred LED: ON: Plug-in jumper position 2-3 OFF: Plug-in jumper position 1-2
Plug-in jumperPosition 1-2: Communication Mode Position 2-3: IR addressing
LED AS-i okoperating display, LED green
FusingT8A/250 V AC HBC (not accessible)
Capacity factor> 0.5
Rated operating voltagenominal: 100 ... 120 V AC/220 ... 240 V AC (front end selectable) permissible: 85 ... 132 V AC/184 ... 264 V AC/230 ... 375 V DC
Rated operating current6,0 A (Switch position 115 V) 2.8 A (Switch position 230 V)
Supply frequency47 ... 63 Hz or DC
Efficiencytyp. 92 % (at 230 V AC/8 A)
Surge protectionlimited to max. 55 V
Short-circuit protection/overloadFUSE Mode (2 ... 5 s current, then trips)
Current limit> 8.4 A
Voltage30.55 V DC ± 3 %
Current8 A
Galvanic isolationovervoltage category III
Residual ripple&le, 50 mVss (500 kHz bandwidth, 50-&Omega,-measurement with ohmic load)
Short-circuit current12 ... 25 A (max. 5 s)
Electromagnetic compatibilityemitted interference in accordance with EN 50081-2 class B (EN 55011, EN 55022) noise immunity in accordance with EN 61000-6-2, EN 61000-4-2 to EN 61000-4-6, EN 61000-4-11
Ambient temperature-10 ... 70 °C (14 ... 158 °F) (Measured 25 mm below the device) from 60° C 6W/°C power recovery necessary
Storage temperature-25 ... 85 °C (-13 ... 185 °F)
Pollution degree2
Degree of protectionIP20 according to EN 60529
Protection class1 (IEC 60536), Protective conductor connection necessary
ConnectionConnection terminals, max. conductor cross-section flexible: 0.5 ... 4 mm2 fixed: 0.5 ... 6 mm2 stripped length 7 mm, connector sleeves are permissible
Material
Housingmetal
Massapprox. 890 g