USER MANUAL
SNV-EKL3.2 Earth fault and short circuit indicator
Description
 SNV-EKL3.2 Earth fault and short circuit indicator, it Widely used in various ring cabinets, high-voltage switch-gear and cable branch box in power system, can accurately and reliably detect the fault section and fault type of power grid. The use of Earth fault and short circuit indicator is an efficient way to check cable fault, and is an effective way to improve the operation level of distribution network and the efficiency of fault handling. The design uses electromagnetic induction, toelectric conversion, iber transmission and single chip microcomputer control technology to make fault alarm with high accuracy and strong anti-interference ability.
Equipped with fault remote transmission port, suitable for distribution network automation; Â Battery low power alarm indication;Â Low-power design, high-capacity lithium battery power supply, long battery life (more than 8 years); external structure using card or lock design, the whole machine is easy to load and unload.
Product Function
1) Intelligent detection of short-circuit and ground fault and through the corresponding LED indicator on the panel to indicate.
2ï¼Display Monitor panel designed with button, it is convenient for reset/or test.
3ï¼It can set The pulse width time(Response time) of fault current for preventing incorrect fault indication caused by surge current.
4ï¼It can set the reset time.
5ï¼It can set the short circuit alarm current via the Dip on short circuit sensor
6ï¼It can set the earth fault alarm current via the Dip on display unit monitor.
7ï¼It can reset and detect the remote fault indication device remotely.
8ï¼It can provide switch volume for external devices through remote relay ï¼
9ï¼Remote fault indicating can be made by external devices.ï¼
10ï¼Low battery display and alarm
Technology Parameter
Voltage grade | 3-40.5KV |  | Battery life | â¥8year | |||
Frequency | 50HZ/60HZ | Low voltage alarm of battery | â¤2.7V | ||||
Short circuit alarm current  (7 levels) | 200/250/300/40A | Short circuit sensor fiber length | 4meter, or customized | ||||
Earth fault alarm current (6 levels) | 10/20/30/40/50/60A ,or customized | Earth fault sensor cable length | 5 meter,or customized | ||||
Reset time (4 levels) | 4H/8H/24/36H | Load fluctuation and escape pulse time setting | Short circuit | 40/60/80/160ms (4 levels) | |||
Rated frequency withstand voltage | 2KV/1min | Earth fault | |||||
Relay capacity | â¤95W | work environment | Temperature | -40â~+60â | |||
Alarm current accuracy | ±10% | Humidity | â¤95%RH | ||||
Working power | ER17505 battery | 3.6V/3500mAh | Use for cable diameter | Short circuit CT (Fiber, Type Sï¼ | A | Ф20mm~40mm, Normally | |
B | Ф300mm~70mm customized | ||||||
Working current | Standby state | â¤10μA | Earth fault sensor (Cable, type E) | A | Ф60mm~100mm Normally | ||
Working state | â¤1mA | ||||||
Indicator protection level | Monitor panel | IP 40 | B | Ф80mm~130mm Customized | |||
Sensor CT | IP 67 |