SNV-EKL3.2 Earth
fault and short circuit indicator
Description
SNV-EKL3.2 Earth fault and short circuit indicator,
it Widely used in various ring cabinets, high-voltage switch-gear and cable branch box in power system, can accurately and reliably detect the fault section and fault
type of power grid. The use of Earth fault and short
circuit indicator is an efficient
way to check cable fault, and is an effective way to improve the operation level of distribution network and the efficiency of fault handling. The design uses electromagnetic induction,
photoelectric conversion, signal optical fiber transmission and single chip microcomputer control technology to make fault alarm with high accuracy and strong anti-interference ability.
Equipped with fault remote transmission port, suitable for distribution network automation; Battery low power alarm indication; Low-power design, high-capacity lithium battery power supply, long battery life (more than 8 years); external structure using card or lock design, the
whole machine is easy to load and unload.
Function character
1) Intelligent detection of short-circuit and ground
fault and through the corresponding LED indicator on the panel to indicate.
2)Display Monitor panel designed with button, it is convenient for reset/or test.
3)It can
set The pulse width time(Response
time) of fault current for preventing incorrect fault indication caused by surge current.
4)It can set the
reset time.
5)It can set the
short circuit alarm current via the Dip on short circuit sensor
6)It can set the
earth fault alarm current via the Dip on display unit monitor.
7)It can reset and detect the remote fault indication device remotely.
8)It can provide switch volume for external devices through remote relay contact.;
9)Remote fault indicating can be made by external devices.;
10)Low battery display and alarm
Function description
1) short circuit alarm indicating: when short circuit sensor detected a short circuit fault current, when the current is greater than or equal to the setting
value, then the short circuit sensor send
alarm signal to monitor panel through fiber. And the monitor will display the alarm signal, the short circuit fault LED will be flash.
2) Earth fault alarm indicating: when the earth fault sensor detected a earth fault current, when the current is
greater than or equal to the setting value, then the earth fault sensor send alarm signal to monitor panel through cable. And the monitor will display the alarm signal, at same time, the earth
fault LED will be flash.
3) Battery low voltage alarm indicating: the monitor use the battery to supply power. When the battery voltage is lower than the min. working voltage 2.7V, then
the Low voltage alarm led will flash.
4)Automatic reset: After the indicator alarm the fault, if there are without manual reset it,
when the time reach our Reset time setting, indicator will
automatically reset.
5) Manual Reset: After the indicator alarm the fault, user can press the button “ reset/test” to reset it.
6)Remote Reset: During indicator indicating
fault, Through the pin 11-12 back of the monitor, connect the remote button to control the indicator
reset.
7)Remote Test: During
indicator on normal condition, Through the pin 11-12 of the monitor, connect the remote button to operate simulation test.
8) Remote indicating fault: Connect an External Lamp on the pin 9-10, when the indicator indicating fault, the External blink
at same time, then achieved long distance indicating fault.
9) Remote upload SCADA: connecting connect pin13-14, or Pin13-15, when indicator indicating fault, A signal will be upload to
SCADA.
Technology parameter
Voltage grade
3-40.5KV
Battery life
≥8year
Frequency
50HZ/60HZ
Low voltage alarm of battery
≤2.7V
Short circuit alarm current
(7 levels)
200/250/300/400/500/600/1000A
Short circuit sensor fiber length
4meter, or customized
Earth fault alarm current
(6 levels)
10/20/30/40/50/60A ,or
customized
Earth fault sensor cable length
5 meter,or customized
Reset time
(4 levels)
4H/8H/24/36H
Load fluctuation and escape pulse time setting
Short circuit
40/60/80/160ms
(4 levels)
Rated frequency withstand voltage
2KV/1min
Earth fault
Relay contact capacity
≤95W
work environment
Temperature
-40℃~+60℃
Alarm current accuracy
±10%
Humidity
≤95%RH
Working power
ER17505
battery
3.6V/3500mAh
Use for cable diameter
Short circuit CT
(Fiber, Type S)
A
Ф20mm~40mm,
Normally
B
Ф300mm~70mm customized
Working current
Standby state
≤10μA
Earth fault sensor
(Cable, type E)
A
Ф60mm~100mm
Normally
Working state
≤1mA
Indicator protection level
Monitor panel
IP 40
B
Ф80mm~130mm
Customized
Sensor CT
IP 67